Standalone CDU

  1. 提供露點以上的供水溫度給制冷背門或水冷板
  2. 內置高效率熱交換器,確保冷卻液品質
  3. 1+1備援泵浦設計,低功耗,運載不停機
  4. 可群控管理
  5. 智能監控,機房內部不結露

產品介紹

  1. 水冷式智能溫控監控主機(CDU)提供機房內部獨立的冷卻循環迴路,由CDU監控供水溫度在機房露點以上,針對機房內部冷卻迴路提供100%顯熱冷卻,無凝結問題,不需加熱或加濕。低耗能、低噪音,低故障且易於維護保養。
  2. 內部主要元件如水泵及變頻器等採備援(1+1)設計,CDU可以常時24小時運作,即時偵測主要元件的運作狀況,遇有突發狀況可立即切換元件繼續運作,不會有因任何元件故障而停機之狀況。可使機房硬體設備需求減少,整體故障機率降低。
  3. CDU並提供業界標準通訊方式,將液冷系統即時運作參數傳輸至機房管理中心,使機房運行管理方便,管理效率更佳。
TC588
Size(H x W x D) 2100(42U) x 800 x 1200mm
Weight 620kg
Cooling Capacity 590kW @ flow rate=500LPM, △T=8°C*
Coolant MGC Coolant THC-00
Pump Dual redundant inverter pump (1+1)
Max. Flow Rate 610 LPM @ △P= 1bar
Water temperature in primary loop 7~12°C
Coolant capacity in 2nd loop 26L
Water temperature in 2nd loop 15~45°C
Pipe connection ISO7241-B Stainless Steel Flange
LCD TP YES
Water Replenishing Yes, built in automation pump
Expansion Tank YES
Venting Manual vent valve
Noise  < 58 dBA (in 3m)
Dew point control YES
Web communication TCP/IP
Modbus Communication RS485 RTU Modbus
Power Consumption 6kW
Power input 380~400V, 50/60 Hz three-phase three-wire AC, 20A pluggable dual-circuit power supply
ATS Model(S) with ATS support
TC988
Size(H x W x D) 2100(42U) x 800 x 1200mm
Weight 660kg
Cooling Capacity 400kW @ flow rate=400LPM, ATD=4°C*
Coolant MGC Coolant THC-00
Pump Dual redundant inverter pump (1+1)
Max. Flow Rate 610 LPM @ △P= 1bar
Water temperature in primary loop 7~12°C, 25~35°C
Coolant capacity in 2nd loop 26L
Water temperature in 2nd loop 15~20°C,  35~45°C
Pipe connection ISO7241-B Stainless Steel Flange
LCD TP YES
Water Replenishing Yes, automatic fill pump
Expansion Tank Yes
Venting Manual Air Vent
Noise  < 58 dBA (in 3m)
Dew point control Yes
Web communication TCP/IP
Modbus Communication RS485 RTU Modbus
Power Consumption 6kW
Power input 380~400V, 50/60 Hz three-phase three-wire AC, 20A pluggable dual-circuit power supply
ATS Model(S) with ATS support
TC1388
Size(H x W x D) 2160(42U) x 900 x 1350mm
Weight 1550kg
Cooling Capacity 1.35MW @ flow rate=1300LPM,ATD=4°C*
Coolant PG25
Pump Triple redundant inverter pumps (2+1)
Max. Flow Rate 1300 LPM @ △P= 0.82bar
Expansion Tank Yes
Venting Manual Air Vent
Noise < 59 dBA (in 3m)
Dew point control Yes
Web communication TCP/IP
Modbus Communication RS485 RTU Modbus
Power Consumption 12.5kW
Power input 380~480V, 50/60 Hz 3-phase
4-wire AC, 25A pluggable dual- circuit power supply
Water temperature in primary loop 7~12°C, 25~35°C
Coolant capacity in 2nd loop 150L
Coolant temperature in 2nd loop 15~20°C,  35~45°C
Pipe connection ISO7241-B Stainless Steel Flange
LCD TP Yes
Coolant Replenishing Yes, automatic fill pump
ATS Optional ATS kit available

台灣總公司

  • 公司電話:+886-3-3181588
  • 客服專線:+886-3-3181588 #808
  • 傳真電話: +886-3-3181585
  • 公司統編: 90573794
  • 33341桃園市龜山區科技二路31號2樓
  • MGCooling@mgcooling.com.tw

分公司據點

高雄元鈦科技有限公司(鼎熒)

台灣.高雄市

高雄市路竹區路科三路7號1樓A室 (南科高雄園區)

蘇州元鈦節能科技有限公司

昆山市

昆山市经济开发区杜鹃路555 号B2幢 3 楼