In-Rack CDU
- 150um filter design to ensure the cleanliness of the coolant inside the cabinet
- Dual-pump (1+1) backup design, running in turn, no need to stop
- Quick disconnect in accordance with ISO7241-B specification, quick installation and easy maintenance
- Unique large 7″ touch LCD screen
- Integrated control system for remote monitoring
- Height 5U/4U, built-in automatic replenishment pump, providing automatic replenishment and low water level alarm
- Variable frequency flow constant temperature control, can be used for warm water cooling
- Automatic control of electric motor valve, manual control of water replenishment system
Product description
M/N | TLS80 | TLS68 |
Size(H x W x D) | 220(5U) x 445 x 925mm | 175(4U) x 445 x 925mm |
Weight | 80kg | 70kg |
Cooling Capacity | 80kW @ flow rate=80LPM, △T=18°C | 60kW @ flow rate=70LPM, △T=18°C |
Coolent | Coolant THC-00 | Coolant THC-00 |
Pump | Dual redundant inverter pump (1+1) | Dual redundant inverter pump (1+1) |
Max. Flow Rate | 80 LPM @ △P= 1bar | 70 LPM @ △P= 1bar |
LCD Moniter | 7″ LCD TP | 7″ LCD TP |
Filter | Yes | Yes |
Water temperature in cabinet | 15~45°C | 15~45°C |
Coolant capacity of the internal circuit of the cabinet | 6L | 6L |
Number of servers managed | 100 sets(0.8LPM per server) | 80 sets(0.8LPM per server) |
Water Replenishing | Yes, built in automation pump | Yes, built in automation pump |
Expansion tank | YES | YES |
Venting | Manual vent valve | Manual vent valve |
Noise | < 58 dBA (in 3m) | < 58 dBA (in 3m) |
Dew point control | YES | YES |
Web communication | TCP/IP | TCP/IP |
Modbus Communication | RS485 RTU Modbus | RS485 RTU Modbus |
Power Consumption | 0.6kW | 1kW |
Power input | 220V,50/60 Hz single phase , 3.15A | 220V,50/60 Hz single phase , 3.15A |
*△T is the temperature difference from pri and 2nd loop.