Air-Cooled CDU
- Capacity: 8kW
- Dual-pump (1+1) backup design, running in turn, no need to stop
- Quick disconnect in accordance with ISO 7241-B specification, quick installation and easy maintenance
- Unique large 7″ touch LCD screen
- Integrated control system for remote monitoring
- Height 8U, built-in automatic replenishment pump, providing automatic replenishment and low water level alarm
- Variable frequency flow constant temperature control, can be used for warm water cooling
- Automatic control of electric motor valve, manual control of water replenishment system
Product description
M/N | AC010 |
Size(H x W x D) | 353(8U) x 447 x 903mm |
Weight | 90kg |
Coolent | Coolant THC-00 |
Cooling capacity | 8kW @ 80LPM |
Pump | Dual redundant inverter pump (1+1) |
Max. flow rate in tank | 80 LPM @ △P= 1bar |
LCD Monitor | 7″ LCD TP |
Water temperature in primary loop | 30~45°C |
Water temperature in 2nd loop | 6L |
Water Replenishing | Built in automation pump |
Expansion tank | YES |
Venting | Manual vent valve |
Noise | < 85 dBA (in 3m) |
Dew point control | YES |
Web communication | TCP/IP |
Modbus Communication | RS485 RTU Modbus |
Power Consumption | 0.6kW |
Power input | 220V,50/60 Hz Single phase , 3.15A |